Category: How to…?

How to Set Up the Pressure Switch Yourself?

Setting up your pressure switch is simple with our dedicated guides. For pressure switches with adjustable hysteresis, refer to our specific guide. For other pressure switch models, we have a comprehensive guide to help you step by step. Remember, a pressure gauge or a pressure transducer is necessary for fine-tuning.

What Happens if I Install the Flow Switch in a Horizontal Position?

Installing the flow switch in a horizontal position can affect its performance. In this position, the force generated by the weight of the shutter is eliminated, leaving the task only to the compensation spring. This means the flow switch may activate at flow rates approximately 20% lower than the actual graduated scale. Additionally, the formation of limescale or other encrustations could hinder the free movement of the shutter.

How to Set Up the Flow Switch Yourself?

Follow these simple steps to set up your flow switch:

  1. Place the cursor at the maximum flow rate.
  2. Set the system’s flow rate to the desired level for the flow switch activation.
  3. Slowly move the cursor down until the switch activates.
  4. Restart the system’s flow and check the switch action again. Make small adjustments by moving the cursor up or down to fine-tune the setup.