The service life and reliability of reed contacts depend on several factors, including the type of load (resistive or inductive), the applied voltage and current, and the presence of any protective circuits, such as capacitors and resistors.
Contact service life can be estimated using specific technical graphs that indicate the number of operating cycles under different operating conditions.
For example, with a resistive load of 50 V DC and 0.5 A, the service life can reach 10⁷ cycles under certain operating conditions.
Although not all manufacturers provide detailed service life curves, when operating within the specified ratings, with purely resistive loads and no current spikes, a service life of at least 10⁵ cycles (100,000 operations) can generally be expected, subject to verification based on the characteristics of the specific reed contact.